APM
 AM
PPCA
 UECA-10-H
 UECA-5-E
UVB
 MCS
SZ
 SSP
    

FLOATING PORTABLE PUMP SET  PPCA

Application:

The pump set is designed to be applied in emergency conditions by fire brigades for pumping water into the tanks of fire engines from natural sources as well as for pumping wather from flooded rooms and for emergency extinguishing. Furthermore, it can be uded in agriculture, in case of failures in water supply and sewerage piping systems, for efficient aeration of water tanks, etc.. With the pump set, polluted water with impurities of the grain size up to 15 mm can be pumped as well and min. height of wather level being 20 mm. It can also operated without liguid ("dry run"), without being seized or overheated.

 

ppca1.jpg (8060 bytes)

Design:

The floating pump is of a light and compact design. It is driven by spark-ignition four -stroke air-cooled engines

-  for lower parameters there is the HONDA GXV 120 (118 cm3, 2,9 kW)

-  for higher parameters there are HONDA GXV 160 (163 cm3, 4 kW).

 

The pump is of centrifugal single-stage type, provided with a discharge branch of diameter 50 mm.

ppca2.jpg (6876 bytes)

Pump set

Technical Data

HONDA GXV 120 HONDA GXV 160
Flow rate

0 - 12 l/s

(max. 720 l/min)

0 - 14,5 l/s

(max. 870 l/min)

Delivery head 14 - 3,5 m 18 - 3,5 m

 Weight

(suchá / pohotovostní)

23,5 / 25,0 kg 26,5 / 28,5 kg

Dimensions

délka / šířka / výška

680x530x375 mm
Fuel petrol unleaded petrol BA 95
Fuel consumption 340 g/kWh (max. 0,9 l/h) 340 g/kWh (max. 1,2 l/h)

GXV 120 and GXV 160 Working charakteristics

 

FLOATING SLUDGE COLLECTOR  PPCA-S

Application:

PPCA-S is an attachement to the floating pump-set PPCA and it is intended for direction and pumping-off a thin film of a liguid on water level. This set is available and suitable for groups liquidating ecological disasters when it is necessary to "cut away" and pump a thin film off a water level (e.g. leaking-out a crude oil being localized by a downflow baffle).

Construction and functioning:

Floating sludge collector PPCA-S consists of a laminate vat and laminate colecting arms being coupled with a hinge and a locking clip allowing its tilting to a transport position, and further there is a tilting manipulation handle. With the aid of collecting arms a polluted  liquid may be supplied to an overflow crest, that will "cut off" the thin film together with other contaminants and will supply it into the van, into which the pump inlet part of the pump-set PPCA enters. For setup of a height of a film that shall be pumped off and for the pump-set  sliding over water level there is the manipulation handle available.

Weight of the attachement:  12 kg

spn3.jpg (33367 bytes)

spn2.jpg (30435 bytes)

spn4.jpg (31497 bytes)

spn1.jpg (27262 bytes)

 

If You require more informations, please contact competent person through the below mentioned email address:

<Business-Economy Department><Hydraulic Research><Construction Department>